5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
127
5
*1 Specification is possible when the host station is a network module or Ethernet module of function version D or later.
(Specification is not possible for other modules. An access is always made to the target station CPU.)
*2 Specification is possible when the versions of the QCPU and the network module on the host station and the target station are as
indicated below.
(Specification is not possible for other modules. An access is always made to the target station CPU.)
Network module: The first five digits of the serial number are '06092' or higher.
QCPU: The first five digits of the serial number are '06092' or higher.
*3 Data are stored only when 1 is set in bit 7 of Error completion type ((s1)[0]).
(s1)[8]
Arrival monitoring time
Specify the monitoring time required for the instruction completion. If the
instruction is not completed within this time, it is resent by the number of times
specified in (s1)[7].
Setting values are as follows.
■
Ethernet
• 0 to 16383
• 0 to TCP retransmission timer value: Monitoring is performed by the TCP
retransmission timer value.
• (TCP retransmission timer value + 1) to 16383: Monitoring time (unit: second)
■
MELSECNET/H
• 0 to 32767
• 0: 10 seconds
• 1 to 32767: 1 to 32767 seconds
0 to 32767
User
(s1)[9]
Read data length
Specify the number of read data.
Setting values are as follows.
• Ethernet, MELSECNET/H, CC-Link IE Field Network: 1 to 960 (word)
• CC-Link IE Controller Network: 1 to 8192 (word)
1 to 8192
User
(s1)[10]
Reserved
User
(s1)[11]
Clock set flag
Valid/invalid status of the data in the area starting from (s1)[12] is stored.
0: Invalid
1: Valid
System
(s1)[12]
(s1)[15]
Clock data at the time
of error completion
Clock data at the time of error completion are stored in BCD format.
System
(s1)[16]
Error-detected network
No.
Network number of the station where an error was detected is stored. (However,
when an error was detected at the host station, the network number is not stored.)
1 to 239: Network number
System
(s1)[17]
Error-detected station
No.
Number of the station where an error was detected is stored. (However, when an
error was detected at the host station, the network number is not stored.)
Stored values are as follows.
• MELSECNET/H: 1 to 64
• Ethernet, CC-Link IE Controller Network: 1 to 120
• Master station in CC-Link IE Field Network: 125 (7DH)
• Local station or the intelligent device station in CC-Link IE Field Network: 1 to
120
System
Device
Item
Setting data
Setting
range
Setting side
b15
b8 b7
to
b0
to
s1
s1
s1
s1
[12]
[13]
[14]
[15]
Month (01
H
to 12
H
)
Year (00
H
to 99
H
) Last two digits
Hour (00
H
to 23
H
)
Day (01
H
to 31
H
)
Second (00
H
to 59
H
)
Minute (00
H
to 59
H
)
Year (00
H
to 99
H
) First two digits
Day of week (00
H
to 06
H
)
00
H
(Sun.) to 06
H
(Sat.)