5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
(s1)[0]
Execution/Error
completion type
Error completion type (bit 7)
Specify the clock data setup status at the time of error completion.
0: Clock data at the time of error completion is not set in the area starting from
(s1)[11].
1: Clock data at the time of error completion is set in the area starting from (s1)[11].
0000H, 0001H,
0080H, 0081H
User
(s1)[1]
Completion
status
The instruction completion status is stored.
0: Normal completion
Other than 0: Error completion (error code)
System
(s1)[2]
Channel used
by host station
Specify the channel used by the host station.
Setting values are as follows.
• Ethernet, MELSECNET/H, CC-Link IE Controller Network: 1 to 8
• CC-Link IE Field Network: 1 to 2
1 to 8
User
(s1)[3]
Target station
channel
Specify the channel of the target station that stores data.*2
Setting values are as follows.
• MELSECNET/H: 1 to 64
• Ethernet, CC-Link IE: 1 to 8
1 to 64
User
(s1)[4]
Target station
network No.
Specify the network number of the target station.
1 to 239: Network number
254: Specify this when 254 has been set in Jn. (Network specified in 'Valid module
during other station access')
1 to 239, 254
User
(s1)[5]
Target station
No.
Specify the station number of the target station.
Setting values are as follows.
■
Station number specification
• MELSECNET/H: 1 to 64
• When the host station is Universal model QCPU in Ethernet or CC-Link IE
Controller Network: 1 to120
• When the host station is anything other than Universal model QCPU in Ethernet or
CC-Link IE Controller Network: 1 to 64
• Master station in CC-Link IE Field Network: 125 (7DH)
• Local station or the intelligent device station in CC-Link IE Field Network: 1 to 120
To increase the data reliability when the station number is specified, executing the
instruction with setting Execution/Error completion type ((s1)[0]) to '1: With arrival
confirmation' is recommended.
■
Group specification (target station is anything other than CC-Link IE Field Network)
81H to A0H: All stations in group numbers 1 to 32
(Setting is available when Execution type is set to '0: Without arrival confirmation' in
(s1)[0].)
■
All stations specification
FFH: All stations of the target network number (Except the host station.)
(Setting is available when Execution type is set to '0: Without arrival confirmation' in
(s1)[0].)
To specify a group or all stations.
• Specify '0000H' or '03FFH' for the target station's CPU type ((s1)[3]).
• Group specification cannot be set for the station of the CC-Link IE Field Network.
• It cannot be confirmed if the data are written to the target station normally. Confirm
the device of the target station of the write destination.
1 to 120, 125
(7DH)
User
(s1)[6]
(Fixed value)
0
User
(s1)[7]
Number of
resends
• For instruction execution
Specify the number of instruction resends when the instruction is not completed within
the monitoring time specified in (s1)[8]. (Setting is available when Execution type is
set to '1: With arrival confirmation' in ((s1)[0].)
0 to 15
User
• At instruction completion
The number of resends (result) is stored. (Setting is available when Execution type is
set to '1: With arrival confirmation' in (s1)[0].)
System
Device
Item
Setting data
Setting
range
Setting side
Group No.1 81
H
Group No.2 82
H
Group No.32 A0
H
to