5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
157
5
Transient request to another station
J(P)_REQ, G(P)_REQ
The following instruction can go in the dotted squares.
J_REQ, JP_REQ, G_REQ, GP_REQ
■
Executing condition
■
Argument
*1 Local devices and file registers per program cannot be used as setting data.
Processing details
Remotely runs or stops a programmable controller on another station.
Also, reads/writes clock data from/to a programmable controller on another station.
Instruction
Executing condition
J_REQ
G_REQ
JP_REQ
GP_REQ
Input/output
argument
Name
Description
Data type
Input argument
EN
Executing condition
Bit
Jn*
Network number of the host station (1 to 239, 254)
254: Network specified in "Valid module during
other station access"
ANY16
Un*
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/
O number in three digits)
ANY16
s1
Variable that stores control data
Array of ANY16 [0..17]
s2
Variable that stores request data
Array of ANY16 [0..5]
Output argument
ENO
Execution result
Bit
d1
Variable that stores response data
Array of ANY16 [0..5]
d2
Variable that turns ON upon completion of the
instruction
d2[1] also turns ON at the time of error completion.
Array of bit [0..1]
Setting
data
Internal device
R, ZR
J
\
U
\G
Zn
Constant
Others
Bit
Word
Bit
Word
(s1)
(s2)
(d1)
(d2)
CC IE F
CC IE C
NET/H
Ether
Structured ladder/FBD
EN
ENO
Jn*
d1
d2
s1
s2
J_REQ
EN
ENO
Un*
d1
d2
s1
s2
G_REQ
ST
J_REQ
(EN, Jn*, s1, s2, d1, d2);
ENO:=
G_REQ
(EN, Un*, s1, s2, d1, d2);
ENO:=