5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
207
5
Setting data
• Send data
Program example
• The following program sends data from the fixed buffer of the connection 1.
(The I/O signals of the Ethernet module are X/Y00 to X/Y1F)
Device
Item
Setting data
Setting
range
Setting
side
(s2)[0]
System area
(s2)[1]
Completion status
The instruction completion status is stored.
0: Normal completion
Other than 0: Error completion (error code)
System
Device
Item
Setting data
Setting
range
Setting
side
(s3)+0
Send data length
Data length of the data read from the fixed buffer data area is stored. (Data length
becomes the number of words or the number of bytes depending on the procedure used in
fixed buffer communication.)
• With procedure (communication in binary code): The number of words (1 to 1017)
• With procedure (communication in ASCII code): The number of words (1 to 508)
• Nonprocedural communication (communication in binary code): The number of bytes (1
to 2046)
(Refer to the
left.)
User
(s3)+1
(s3)+n
Send data
Specify the send data.
User
[Structured ladder/FBD]
Send instruction
1PLS
Sets send data
Sets data length
(number of words)
Sends data in
fixed buffer
communication
Normal completion
Error completion
Process on normal completion
Process on error completion