5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
Setting data
Device
Item
Setting data
Setting
range
Setting side
(s1)[0]
Error completion
type
Error completion type (bit 7)
Specify the clock data setup status at the time of error completion.
0: Clock data at the time of error completion is not set in the area starting from
(s1)[11].
1: Clock data at the time of error completion is set in the area starting from (s1)[11].
0011H, 0091H
User
(s1)[1]
Completion
status
The instruction completion status is stored.
0: Normal completion
Other than 0: Error completion (error code)
System
(s1)[2]
Channel used
by host station
Specify the channel used by the host station.
1 to 8: Channel
1 to 8
User
(s1)[3]
Target station's
CPU type
Specify the type of the target station CPU.
Setting values are as follows.
■
Ethernet
• 0000H: Target station CPU/host system CPU (Specified data are the same as
'03FFH'.)
• 03FFH
: Target station CPU/host system CPU
■
MELSECNET/H CC-Link IE
• 0000H: Target station CPU/host system CPU (Specified data are the same as
'03FFH'.)
• 03E0H
: Multi-CPU No. 1/target station CPU (single CPU system)
• 03E1H
: Multi-CPU No. 2
• 03E2H
: Multi-CPU No. 3
• 03E3H
: Multi-CPU No. 4
• 03FFH
: Target station CPU/host system CPU
■
Ethernet
0000H,03FFH
■
MELSECNE
T/H, CC-Link
IE
0000H, 03E0H
to 03E3H,
03FFH
User
(s1)[4]
Target station
network No.
Specify the network number of the target station.
1 to 239: Network number
254: Specify this when 254 has been set in Jn. (Network specified in 'Valid module
during other station access')
1 to 239, 254
User
(s1)[5]
Target station
No.
Specify the station number of the target station.
Setting values are as follows.
■
Station number specification
• MELSECNET/H: 1 to 64
• When the host station is Universal model QCPU in Ethernet or CC-Link IE
Controller Network: 1 to120
• When the host station is anything other than Universal model QCPU in Ethernet or
CC-Link IE Controller Network: 1 to 64
• Master station in CC-Link IE Field Network: 125 (7DH)
• Local station or the intelligent device station in CC-Link IE Field Network: 1 to 120
■
Group specification (target station is anything other than CC-Link IE Field Network)
81H to A0H: All stations in group numbers 1 to 32 (Available only at clock data writing
and remote RUN/STOP)
■
All stations specification
FFH: All stations of the target network number (Except the host station.) (Available
only at clock data writing and remote RUN/STOP)
To specify a group or all stations.
• Specify '0000H' or '03FFH' for the target station's CPU type ((s1)[3]).
• Group specification cannot be set for the station of the CC-Link IE Field Network.
• It cannot be confirmed if the data are written to the target station normally. Confirm
the device of the target station of the write destination.
1 to 120, 125
(7DH), 81H to
A0H, FFH
User
(s1)[6]
(Fixed value)
0
User
(s1)[7]
Number of
resends
• For instruction execution
Specify the number of resends when the instruction is not completed within the
monitoring time specified in (s1)[8].
0 to 15
User
• At instruction completion
The number of resends (result) is stored
0 to 15
System
b15
0
0
(1)
1
0
1
b7
b0
b4
…
…
…
Group No.1 81
H
Group No.2 82
H
Group No.32 A0
H
to