5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
159
5
*1 Specification is possible when the host station is a network module or Ethernet module of function version D or later.
(Specification is not possible for other modules. An access is always made to the target station CPU.)
*2 Specification is possible when the versions of the QCPU and the network module on the host station and the target station are as
indicated below.
(Specification is not possible for other modules. An access is always made to the target station CPU.)
Network module: The first five digits of the serial number are '06092' or higher.
QCPU: The first five digits of the serial number are '06092' or higher.
*3 This becomes valid only when 1 is set in bit 7 of Error completion type ((s1)[0]).
(s1)[8]
Arrival
monitoring time
Specify the monitoring time required for the instruction completion.
If the instruction is not completed within this time, it is resent by the number of times
specified in (s1)[7].
Setting values are as follows.
■
Ethernet
• 0 to 16383
• 0 to TCP retransmission timer value: Monitoring is performed by the TCP
retransmission timer value.
• (TCP retransmission timer value + 1) to 16383: Monitoring time (unit: second)
■
MELSECNET/H CC-Link IE
• 0 to 32767
• 0: 10 seconds
• 1 to 32767: 1 to 32767 seconds
0 to 32767
User
(s1)[9]
Request data
length
Specify the number of request data (words).
(Number of words of data stored in the request data storage device (s2))
4: Remote RUN
3: Remote STOP
2: Clock data read
6: Clock data write
2 to 4, 6
User
(s1)[10]
Response data
length
Number of response data (words) are stored.
(Number of words of the data stored in response data storage device)
2: Remote RUN/STOP
6: Clock data read
2: Clock data write
System
(s1)[11]
Clock set flag
Valid/invalid status of the data in the area starting from (s1)[12] is stored.
0: Invalid
1: Valid
System
(s1)[12]
(s1)[15]
Clock data on
error
completion
Clock data at the time of error completion are stored in BCD format.
System
(s1)[16]
Error-detected
network No.
Network number of the station where an error was detected is stored. (However,
when an error was detected at the host station, the network number is not stored.)
1 to 239: Network number
System
(s1)[17]
Error-detected
station No.
Number of the station where an error was detected is stored. (However, when an
error was detected at the host station, the network number is not stored.)
Stored values are as follows.
• MELSECNET/H: 1 to 64
• Ethernet, CC-Link IE Controller Network: 1 to 120
• Master station in CC-Link IE Field Network: 125 (7DH)
• Slave station in CC-Link IE Field Network: 1 to 120
System
Device
Item
Setting data
Setting
range
Setting side
b15
b8 b7
to
b0
to
s1
s1
s1
s1
Month (01
H
to 12
H
)
Hour (00
H
to 23
H
)
Second (00
H
to 59
H
)
Year (00
H
to 99
H
) First two digits
Year (00
H
to 99
H
) Last two digits
Day (01
H
to 31
H
)
Minute (00
H
to 59
H
)
Day of week (00
H
to 06
H
)
00
H
(Sun.) to 06
H
(Sat.)
[12 ]
[13 ]
[14 ]
[15 ]