5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
175
5
■
Argument
*1 Local devices and file registers per program cannot be used as setting data.
Processing details
This instruction remotely switches a CPU module on another station to STOP.
Precautions
This instruction is applicable to the QJ71LP21 or QJ71BR11 with the function version B or later.
Input/output
argument
Name
Description
Data type
Input argument
EN
Executing condition
Bit
Jn*
Network number of the host station (1 to 239)
254: Network specified in "Valid module during
other station access"
String
Un*
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/
O number in three digits)
String
s1
Channel used by host station
ANY16
s2
Target station number
(1) Station number specification
Host station is Universal model QCPU: 1 to 120
Host station is anything other than Universal model
QCPU: 1 to 64
(2) Group specification
81H to A0H: All stations of a group (No.1 to 32)
(3) All stations
FFH: All stations of the target network No. (Except
the host station)
ANY16
s3
Target station's CPU type
0000H: Target station CPU/control CPU/host
system CPU (Specified data are the same as
'03FFH'.)
03E0H: Multi-CPU No. 1/target station CPU (single
CPU system)
03E1H: Multi-CPU No. 2
03E2H: Multi-CPU No. 3
03E3H: Multi-CPU No. 4
03FFH: Target station CPU/control CPU/host
system CPU
ANY16
s4
Specify options for the operation mode and clear
mode.
(1) Operation mode
1H: No forced execution
3H: Forced execution
(2) Clear mode
0H: Do not clear (Note that the local devices are
cleared.)
1H: Clear (excluding the latch range)
2H: Clear (including the latch range)
ANY16
Output argument
ENO
Execution result
Bit
d
Variable that turns ON upon completion of the
instruction
d[1] also turns ON at the time of error completion.
Array of bit [0..1]
Setting
data
Internal device
R, ZR
J
\
U
\G
Zn
Constant
K, H
Others
Bit
Word
Bit
Word
(s1)
(s2)
(s3)
(s4)
(d)