5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
137
5
*1 Specification is possible when the host station is a network module or Ethernet module of function version D or later.
(Specification is not possible for other modules. An access is always made to the target station CPU.)
*2 Specification is possible when the versions of the QCPU and the network module on the host station and the target station are as
indicated below.
(Specification is not possible for other modules. An access is always made to the target station CPU.)
Network module: The first five digits of the serial number are '06092' or higher.
QCPU: The first five digits of the serial number are '06092' or higher.
*3 Data are stored only when 1 is set in bit 7 of Error completion type ((s1)[0]).
(s1)[7]
Number of resends
• For instruction execution
Specify the number of instruction resends when the instruction is not completed within
the monitoring time specified in (s1)[8]. (Setting is available when Execution type is set
to '1: With arrival confirmation' in ((s1)[0].)
0 to 15
User
• At instruction completion
The number of resends (result) is stored. (Setting is available when Execution type is
set to '1: With arrival confirmation' in (s1)[0].)
System
(s1)[8]
Arrival monitoring time
Specify the monitoring time required for instruction completion. (Setting is available
when Execution type is set to '1: With arrival confirmation' in ((s1)[0].)
If the instruction is not completed within this time, it is resent by the number of times
specified in (s1)[7].
Setting values are as follows.
■
Ethernet
• 0 to 16383
• 0 to TCP retransmission timer value: Monitoring is performed by the TCP
retransmission timer value.
• (TCP retransmission timer value + 1) to 16383: Monitoring time (unit: second)
■
MELSECNET/H
• 0 to 32767
• 0: 10 seconds
• 1 to 32767: 1 to 32767 seconds
0 to 32767
User
(s1)[9]
Write data length
Specify the number of write data.
Setting values are as follows.
• Ethernet, MELSECNET/H, CC-Link IE Field Network: 1 to 960 (word)
• CC-Link IE Controller Network: 1 to 8192 (word)
User
(s1)[10]
(Reserved)
(s1)[11]
Clock set flag
Valid/invalid status of the data in the area starting from (s1)[12] is stored.
0: Invalid
1: Valid
System
(s1)[12]
(s1)[15]
Clock data at the time of
error completion
Clock data at the time of error completion are stored in BCD format.
System
(s1)[16]
Error-detected network
No.
Network number of the station where an error was detected is stored. (However, when
an error was detected at the host station, the network number is not stored.)
1 to 239: Network number
System
(s1)[17]
Error-detected station
No.
Number of the station where an error was detected is stored. (However, when an error
was detected at the host station, the network number is not stored.)
Stored values are as follows.
• MELSECNET/H: 1 to 64
• Ethernet, CC-Link IE Controller Network: 1 to 120
• Master station in CC-Link IE Field Network: 125 (7DH)
• Local station or the intelligent device station in CC-Link IE Field Network: 1 to 120
System
Device
Item
Setting data
Setting
range
Setting
side
[
12
]
[
13
]
[
1
4 ]
[
1
5 ]
b
1
5
b
8
b7
to
b
0
to
s1
s1
s1
s1
M
ont
h (
01
H
to
12
H
)
H
our
(
00
H
to
23
H
)
S
econd
(
00
H
to
59
H
)
Y
ear
(
00
H
to
99
H
) Fi
rst
t
w
o
d
i
g
i
ts
Y
ear
(
00
H
to
99
H
) L
ast
t
w
o
d
i
g
i
ts
D
ay
(
01
H
to
31
H
)
Mi
nute
(
00
H
to
59
H
)
D
ay
o
f w
ee
k (
00
H
to
0
6
H
)
00
H
(S
un
.)
to
0
6
H
(S
at
.)