5. PARAMETERS
5.7 (N) Communication operation parameters
General flowchart
CAUTION
• Always set the communication check time interval before starting operation to prevent hazardous conditions.
• Data communication is not started automatically but is made only once when the computer provides a communication
request. If communication is disabled during operation due to signal cable breakage etc., the inverter cannot be stopped.
When the communication check time interval has elapsed, the inverter output will be shut off (E.PUE, E.SER).
Turn the RES signal of the inverter ON or shut off the power supply to coast the motor to a stop.
• Note that the converter unit does not detect a fault if communication is broken due to signal cable breakage, computer
fault etc.
Port open
Communication setting
Time out setting
Send data processing
Receive data waiting
Receive data processing
○Data setting
○Sum code calculation
○Data transmission
○Receive data processing
○Screen display