41
2. INSTALLATION AND WIRING
2.6 Control circuit
1
2
3
4
5
6
7
8
9
10
(The output signals may be used in either the sink or source logic independently of the jumper connector position.)
NOTE
• Make sure that the jumper connector is installed correctly.
• Never change the control logic while power is ON.
Sink logic and source logic
• In the sink logic, a signal turns ON when a current exits from the corresponding signal input terminal.
Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals.
• In the source logic, a signal turns ON when a current enters into the corresponding signal input terminal.
Terminal PC is common to the contact input signals. Terminal SE is common to the open collector output signals.
Jumper connector
SOURCE
SINK
For sink logic
PC
RES
R
RDI
R
SD
RES
R
RDI
R
PC
X10
R
RES
R
RDA
SE
Converter unit
Inverter
Converter unit
Inverter
SD
RES
R
X10
R
RDA
SE
Current
Source logic
Source
connector
Source
connector
Current
Sink
connector
Sink
connector
Sink logic
Current flow concerning the input/output signal
when sink logic is selected
Current flow concerning the input/output signal
when source logic is selected
Current flow
Current flow
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...