5. PARAMETERS
5.6 (A) Application parameters
Connection and parameter setting
• Remove the jumpers between terminals R/L1 and R1/L11 and terminals S/L2 and S1/L21 of the converter unit, and
connect terminals R1/L11 and P/+ and terminals S1/L21 and N/-. Do not remove the jumpers of terminal R1/L11 and
terminal S1/L21 of the inverter. (In the initial status of the inverter, terminals P/+ and R1/L11 and terminals N/- and S1/L21
are connected.)
• Connect the terminal to which PWF signal of the converter unit is assigned and the terminal to which X48 signal of the
inverter is assigned. Also, set
Pr.261
of the converter unit in accordance with the inverter setting.
Power failure stop signal (PWF signal)
• The Power failure stop (PWF) signal turns ON during instantaneous power failure, undervoltage, or input phase loss.
• To use the PWF signal, set "210" (positive logic) or "310" (negative logic) in any parameter from
Pr.190 to Pr.195 (Output
terminal function selection)
to assign the function.
When the input specification of the Power failure stop external (X48) signal of the inverter is the NC contact, set the
negative logic for the PWF signal of the converter unit. When the input specification of the inverter's X48 signal is the NO
contact, set the positive logic for the PWF signal of the converter unit. (For the X48 signal, the initial setting is the NC
contact input specification. For changing the input logic, refer to the Instruction Manual of the inverter.)
NOTE
• When the power failure time deceleration stop function is selected, undervoltage protection (E.UVT), instantaneous power
failure protection (E.IPF) and input phase loss protection (E.ILF) are invalid.
• Changing the terminal assignment using
Pr.190 to Pr.195 (Output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.195 (Output terminal function selection)
Pr.872 Input phase loss protection selection
Power supply
Remove the jumper
Converter unit
Inverter
R/L1
S/L2
T/L3
R1/L11
S1/L21
U
V
W
M
R1/L11
S1/L21
P/+
N/-
P/+
N/-
Connect terminals
R1/L11 and P/+
and terminals
S1/L21 and N/-.
Keep the jumpers between
terminals R1/L11 and S1/L21
connected.
RDA
MRS(X10)
RSO
RES
PWF
X48
SE
SD
Pr.261 setting
Description
Power failure time deceleration-to-stop function when the
automatic restart after instantaneous power failure is
enabled (Pr.57
≠
"9999").
Inverter
Converter unit
0
0
Power failure time
deceleration-to-stop
function disabled
—
1, 11
1
Power failure time
deceleration-to-stop
function enabled
Disabled
2, 12
2
Enabled
21
21
Disabled
22
22
Enabled
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...