147
6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
1
2
3
4
5
6
7
8
9
10
Operation panel
indication
E.ILF
Name
Input phase loss
Description
When
Pr.872 Input phase loss protection selection
is enabled ("1") and one of the three-phase power input
is lost, the inverter output is shut off. This protective function is not available when
Pr.872
is set to the initial value
(
Pr.872
= "0"). (Refer to
.)
Check point
Check for a break in the cable for the three-phase power supply input.
Corrective action
• Wire the cables properly.
• Repair a break portion in the cable.
Operation panel
indication
E.OHT
Name
External thermal relay operation
Description
While "1" (NC contact) or "2" (NO contact) is set in
Pr.876 OH input selection
to enable the function, the inverter
output is shut off if output of the device such as a thermostat is input as the OH signal, and the OH signal turns
ON (NO contact input) or turns OFF (NC contact input).
The OH signal function is assigned to the terminal OH in the initial status.
This protective function is not available when
Pr.876
is set to the initial value (
Pr.876
= "0"). (Refer to
.)
Check point
• Check for overheating of the thermostat for overheat protection of peripheral devices.
• Check that the value "7" (OH signal) is set correctly to any of
Pr.178, Pr.187
or
Pr.189 (Input terminal function
selection)
.
Corrective action
• Reduce the load and operation duty.
• Even if the thermostat automatically returns to normal, the converter unit (inverter) will not restart unless it is
reset.
Operation panel
indication
E.PE
Name
Parameter storage device fault (control circuit board)
Description
The inverter output is shut off if a fault occurs in the parameter stored. (EEPROM failure)
Check point
Check for too many number of parameter write times.
Corrective action
Contact your sales representative.
Set "1" in
Pr.342 Communication EEPROM write selection
(write to RAM) for the operation which requires
frequent parameter writing via communication, etc. Note that writing to RAM goes back to the initial status at
power OFF.
Operation panel
indication
E.PUE
Name
PU disconnection
Description
• The inverter output is shut off if communication between the operation panel and the converter unit is
interrupted (e.g. by removing the operation panel) when the disconnected PU detection function is valid in
Pr.75 Reset selection/disconnected PU detection/reset limit
.
• The inverter output is shut off if communication errors occurred consecutively for more than permissible
number of retries when
Pr.121 PU communication retry count
≠
"9999" during the RS-485 communication.
• The inverter output is shut off if communication is broken within the period of time set in
Pr.122 PU
communication check time interval
during the RS-485 communication via the PU connector.
Check point
• Check that the operation panel is connected properly.
• Check the
Pr.75
setting.
Corrective action
Connect the operation panel securely.
Operation panel
indication
E.RET
Name
Retry count excess
Description
The inverter output is shut off if the operation cannot be resumed properly within the number of retries set in
Pr.67
Number of retries at fault occurrence
. This function is available when
Pr.67
is set. This protective function is
not available in the initial setting (
Pr.67
= "0").
Check point
Find the cause of the fault occurrence.
Corrective action
Eliminate the cause of the fault preceding this fault indication.
Operation panel
indication
E.PE2
Name
Parameter storage device fault (main circuit board)
Description
The inverter output is shut off if a fault occurs in the parameter stored. (EEPROM failure)
Check point
――――
Corrective action
Contact your sales representative.
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...