108
5. PARAMETERS
5.7 (N) Communication operation parameters
Parameters related to RS-485 terminal communication
*1
When "1" (MODBUS RTU protocol) is set in
Pr.549
, the setting range within parentheses is applied.
*2
When a value outside the setting range is set, the converter operates at the initial value.
*3
In the MODBUS RTU protocol, the data length is fixed at 8 bits.
*4
In the MODBUS RTU protocol,
Pr.334
setting is applied as the stop bit length. (Refer to
.)
*5
In the MODBUS RTU protocol, this is invalid.
NOTE
• The monitor items and parameter settings can be read during communication with the
Pr.336 RS-485 communication check
time interval
= "0 (initial value)" setting, but a converter unit communication error (E.SER) occurs. To perform operation or
parameter writing via communication, set "9999" or a large setting value in
Pr.336
. (The setting value is determined by the
computer program.) (Refer to
.)
• Always reset the converter after making the initial settings of the parameters. After changing the communication-related
parameters, communication cannot be made until the converter is reset.
5.7.5
Mitsubishi inverter protocol (computer link
communication)
Parameter setting and monitoring, etc. are possible through communication using the Mitsubishi inverter protocol (computer
link communication) via the PU connector or RS-485 terminals on the converter unit.
Pr.
Name
Initial
value
Setting
range
Description
331
N030
RS-485 communication
station number
0
0 to 31 (0 to
247)
Specify the converter unit station number.
(Same specifications as
Pr.117
)
332
N031
RS-485 communication
speed
96
3, 6, 12, 24,
48, 96, 192,
384, 576,
768, 1152
Select the communication speed.
(Same specifications as
Pr.118
)
N032
RS-485 communication
data length
0
0, 1
Select the data length. (Same specifications as
P.N022
)
N033
RS-485 communication
stop bit length
1
0, 1
Select the stop bit length. (Same specifications as
P.N023
333
RS-485 communication
stop bit length / data
length
1
0, 1, 10, 11
Select the stop bit length and data bit length. (Same specifications as
Pr.119
334
N034
RS-485 communication
parity check selection
2
0, 1, 2
Select the parity check specifications.
(Same specifications as
Pr.120
)
335
N035
RS-485 communication
retry count
1
0 to 10,
9999
Set the permissible number of retries for unsuccessful data reception.
(Same specifications as
Pr.121
)
336
N036
RS-485 communication
check time interval
0 s
0
The RS-485 communication is available, but a communication error occurs.
0.1 to 999.8
s
Set the interval of the communication check (signal loss detection) time
(Same specifications as
Pr.122
)
9999
No communication check (signal loss detection)
337
N037
RS-485 communication
waiting time setting
9999
0 to 150 ms,
9999
Set the time delay between data transmission to the converter unit and the
response. (Same specifications as
Pr.123
)
341
N038
RS-485 communication
CR/LF selection
1
0, 1, 2
Select the presence/absence of CR/LF.
(Same specifications as
Pr.124
)
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...