94
5. PARAMETERS
5.4 (M) Item and output signal for monitoring
• The ALM signal is initially assigned to the relay terminals A1, B1, and C1.
NOTE
• For the details of the converter unit faults, refer to
5.4.3
Detection of control circuit temperature
The temperature of the control circuit board of the converter unit can be monitored, and a signal can be output according to the
predetermined temperature setting.
Control circuit temperature monitoring
• The operation panel can be used to monitor the temperature of the control circuit board within the range of 0°C to 100°C.
• The range becomes -20°C to 100°C by setting the display with a minus sign in
Pr.290 Monitor negative output selection
.
Control circuit temperature detection (Pr.663, Y207 signal)
• The Y207 signal can be output when the control circuit temperature reaches the
Pr.663
setting or higher.
• To use the Y207 signal, set "207" (positive logic) or "307" (negative logic) in any parameter from
Pr.190 to Pr.195 (Output
terminal function selection)
to assign the function to the output terminal.
NOTE
• The Y207 signal is turned OFF when the control circuit temperature becomes 5°C or more lower than the
Pr.663
setting.
• Changing the terminal assignment using
Pr.190 to Pr.195 (Output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.195 (Output terminal function selection)
Pr.290 Monitor negative output selection
ON
Reset processing
(about 1s)
OFF
ON
ON OFF
Reset ON
ALM
ALM2
RES
OFF
Converter unit fault occurrence
(trip)
Pr.
Name
Initial value
Setting range
Description
663
M060
Control circuit temperature
signal output level
0°C
0°C to 100°C
Set the temperature where the Y207 signal turns
ON.
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...