3. PRECAUTIONS FOR USE OF THE CONVERTER UNIT
3.1 Electro-magnetic interference (EMI) and leakage currents
1
2
3
4
5
6
7
8
9
10
• Specification example (ZCAT3035-1330 manufactured by TDK)
The impedance values above are reference values, and not guaranteed values.
EMI measure example
NOTE
• For compliance with the EU EMC Directive, refer to
.
3.1.3
Built-in EMC filter
The converter unit (FR-CC2) is equipped with a built-in EMC filter (capacitive filter).
These filters are effective in reducing air-propagated noise on the input side of the converter unit.
Two female connectors are initially connected to the OFF (disabled) male connectors.
To enable the EMC filter, fit both of the EMC filter ON/OFF connectors to the "enabled" (ON) position.
Item
Description
Impedance (
Ω
)
10 to 100 MHz
80
100 to 500 MHz
150
Outline dimension drawings
(mm)
34
1
TDK
39
1
Product name
Lot number
30
1
Cable fixing band
mount
13
1
Inverter
Converter
unit
Line noise
filter
Sensor
Use 4-core cable for motor
power cable and use one
cable as earth (ground) cable.
Use a twisted pair shielded cable
Inverter
power
supply
Do not earth (ground) shield but
connect it to signal common cable.
Enclosure
Decrease carrier frequency
Motor
M
Install the line noise filter
on inverter output side.
Separate inverter, converter
unit, and power line by more
than 30 cm from sensor circuit.
(at least 10 cm)
Control
power
supply
Do not earth (ground) enclosure directly.
Do not earth (ground) control cable.
Power
supply for
sensor
EMC
filter
EMC filter OFF
EMC filter ON
FILTER
OFF
ON
FILTER
OFF
ON
EMC filter ON/OFF connector
EMC filter ON/OFF connector
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...