95
5. PARAMETERS
5.5 (T) Multi-function input terminal parameters
1
2
3
4
5
6
7
8
9
10
5.5
(T) Multi-function input terminal parameters
5.5.1
Input terminal function selection
Use the following parameters to select or change the input terminal functions.
Input terminal function assignment
• Using
Pr.178, Pr.187, and Pr.189
, set the functions of the input terminals.
• Refer to the following table and set the parameters.
*1
The OH signal is activated when the relay contact is open.
NOTE
• The same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
• When the terminal assignment is changed with
Pr.178, Pr.187
, or
Pr.189 (Input terminal function selection)
, wiring may be
mistaken due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming
the function of each terminal.
5.5.2
Operation selection for the external thermal relay
input (Pr.876)
The operation when the external thermal relay input (OH) signal is input can be changed by the
Pr.876
setting.
Purpose
Parameter to set
Refer to
page
To assign functions to input terminals
Input terminal function
selection
P.T700, P.T709,
P.T711
Pr.178, Pr.187,
Pr.189
To change operation when the OH signal
is input
OH input selection
P.T723
Pr.876
Pr.
Name
Initial
value
Signal name
Setting range
178
T700
RDI terminal
function selection
9999
Function disabled.
7, 62, 9999
187
T709
OH terminal function
selection
7
OH (External thermal relay input)
189
T711
RES terminal
function selection
62
RES (Converter reset)
Setting
Signal
name
Function
Related parameter
Refer to
page
7
OH
External thermal relay input
Pr.876
62
RES
Converter reset
—
9999
—
Function disabled.
—
—
Pr.
Name
Initial
value
Setting
range
Description
876
T723
OH input selection
0
0
Function disabled.
1
NC contact: Turning OFF of the OH signal stops the
converter unit operation after a fault occurs.
2
NO contact: Turning ON of the OH signal stops the converter
unit operation after a fault occurs.
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...