88
5. PARAMETERS
5.4 (M) Item and output signal for monitoring
*1
The cumulative energization time is accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
*2
Since each readout of the output voltage and output current displayed on the operation panel is a four-digit number, a value of more than 9999
is displayed as "----".
*3
0 A appears during regenerative driving.
*4
The details of bits for the input terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the converter. "—" denotes an indefinite
(null) value.)
*5
The details of bits for the output terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the converter. "—" denotes an indefinite
(null) value.)
*6
The monitor value is retained when an converter unit fault occurs. Resetting clears the retained values.
Monitor item
Increment
and unit
Pr.
setting
RS-485
MODBUS
RTU
Negative
indication
(-)
Description
Input current
0.1 A
2
H02
40202
The converter unit input current effective value is
displayed.
Converter output
voltage
0.1 V
8
H08
40208
The DC bus voltage value is displayed.
Input power
0.1 kW
13
H0D
40213
The power at the converter unit input side is displayed.
Cumulative
energization time
1 h
20
H14
40220
The cumulative energization time since the converter unit
shipment is displayed. The number of times an
integrated value has reached the maximum value of
65535 hours can be checked in
Pr.563
.
Cumulative energy
0.1 kWh
25
H19
40225
The cumulative energy based on the monitored input
power is displayed. Use
Pr.170
Station number (RS-
485 terminals)
1
43
H2B
40243
The station number (0 to 31) of the converter unit
enabling communication via the RS-485 terminals is
displayed.
Station number (PU)
1
44
H2C
40244
The station number (0 to 31) of the converter unit
enabling communication via the PU connector is
displayed.
Input terminal status
—
55
H0F
40215
The ON/OFF state of the input terminals on the converter
unit is displayed. (Refer to
for details of
indication on the operation panel.)
Output terminal
status
—
H10
40216
The ON/OFF state of the output terminals on the
converter unit is displayed. (Refer to
for details
of indication on the operation panel.)
Electronic thermal O/
L relay load factor
0.1%
62
H3E
40262
The accumulated heat value of the converter thermal O/
L relay is displayed.
The Converter overload trip (electronic thermal relay
function) (E.THT) occurs at 100%.
32-bit cumulative
energy (lower 16 bits)
1 kWh
—
H4D
40277
The upper or lower 16 bits of the 32-bit cumulative
energy is displayed on each indication.
It is monitored via RS-485 communication.
32-bit cumulative
energy (upper 16 bits)
1 kWh
—
H4E
40278
32-bit cumulative
energy (lower 16 bits)
0.1 kWh
—
H4F
40279
32-bit cumulative
energy (upper 16 bits)
0.1 kWh
—
H50
40280
Control circuit
temperature
1°C
98
H62
40298
○
The temperature of the control circuit board is displayed.
When negative number not displayed: 0°C to 100°C
When negative number displayed: -20°C to 100°C
b15
b0
-
-
-
-
RES
-
OH
-
-
-
-
-
-
-
RDI
-
b15
b0
-
-
-
-
-
-
-
-
-
ABC1
FAN
RSO
IPF
RDA
RDB
-
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...