117
5. PARAMETERS
5.7 (N) Communication operation parameters
1
2
3
4
5
6
7
8
9
10
Setting items and set data
• After completion of parameter settings, set the instruction codes and data, then start communication from the computer to
allow reading/writing of parameters and monitoring.
Item
Read/
write
Instruction
code
Data description
Number of data
digits (format)
Monitor
Converter
output voltage
Read
H6F
H0000 to HFFFF: Converter output voltage (hexadecimal) in 0.1 V
increments
4 digits (B and E/D)
Input current
Read
H70
H0000 to HFFFF: Output current (hexadecimal) in 0.1 A increments
4 digits (B and E/D)
Electronic
thermal O/L
relay load factor
Read
H71
H0000 to HFFFF: Electronic thermal relay function load factor
(hexadecimal) in 0.1% increments
4 digits (B and E/D)
Special monitor Read
H72
H0000 to HFFFF: Monitor data selected in the instruction code HF3
4 digits (B and E/D)
Special monitor
selection No.
Read
H73
Monitor selection data (Refer to
for details on selection No.)
2 digits (B and E1/D)
Write
HF3
2 digits (A1 and C/
D)
Fault record
Read
H74 to H77
H0000 to HFFFF: Two fault records per code.
(Refer to
for details on fault record read data.)
4 digits (B and E/D)
Converter status
monitor (extended)
Read
H79
The status of output signals can be monitored. (For the details, refer to
.)
4 digits (B and E/D)
Converter status
monitor
Read
H7A
2 digits (B and E1/D)
Converter reset
Write
HFD
H9696: Converter unit reset
As the converter unit is reset at the start of communication by the
computer, the converter unit cannot send reply data back to the computer.
4 digits (A and C/D)
H9966: Converter unit reset
After the computer correctly starts communication and send data to the
converter, the converter unit returns the ACK signal to the computer
before being reset.
4 digits (A and D)
Fault history clear
Write
HF4
H9696: Fault history is cleared.
4 digits (A and C/D)
b15
b8 b7
b0
Latest fault
Second latest fault
Third latest fault
Fourth latest fault
Fifth latest fault
Sixth latest fault
Seventh latest fault
Eighth latest fault
H74
H75
H76
H77
With the read data H3040
Fault record display example (instruction code H74)
(Second fault: E.THC)
(Latest fault: E.FIN)
0
b15
Latest fault
(H40)
Second fault
(H30)
0 1 1 0 0 0 0
b8
0
b7
1 0 0 0 0 0 0
b0
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...