10. Additional refrigerant charge
At the time of shipping, the outdoor unit is charged with refrigerant.
This charge does not include the amount needed for extended piping and
additional charging of each refrigerant line will be required on site. In order that
future servicing may be properly provided, always keep a record of the size and
length of each refrigerant line and the amount of additional charge by writing it in
the space provided on the outdoor unit.
10.1. Calculation of additional refrigerant
charge
Calculate the amount of additional charge based on the length of the piping
extension and the size of the refrigerant line.
Use the table below as a guide for calculating the amount of additional
charging and then charge the system accordingly.
If the calculation results in a fraction of less than 0.1 kg, round up to the next
0.1 kg. For example, if the result of the calculation was 30.73 kg, round the
result up to 30.8 kg.
•
•
•
<Additional charge>
Additional refrigerant
charge
=
High-pressure
pipe size
Total length of ø28.58
×0.36
+
High-pressure
pipe size
Total length of ø22.2
×0.23
+
High-pressure
pipe size
Total length of ø19.05
×0.16
+
High-pressure
pipe size
Total length of ø15.88
×0.11
+
Liquid Piping Size
Total length of ø15.88
×0.2
(kg)
(m)×0.36(kg/m)
(m)×0.23(kg/m)
(m)×0.16(kg/m)
(m)×0.11(kg/m)
(m)×0.2(kg/m)
+
Liquid Piping Size
Total length of ø12.7
×0.12
+
Liquid Piping Size
Total length of ø9.52
×0.06
+
Liquid Piping Size
Total length of ø6.35
×0.024
(m)×0.12(kg/m)
(m)×0.06(kg/m)
(m)×0.024(kg/m)
+
Total Outdoor Unit
Model Name
BC controller
(Standard/Main)
Per Unit
+
BC controller
(Main) HA-type
+
BC controller
(Sub) Total Units
BC controller
(Sub) Per Unit
+
Total Capacity of
Connected Indoor Units
Per Indoor
Unit
~80
2.0kg
(E)P200
2.0kg
2.0 kg
1
1.0 kg
81~160
2.5kg
(E)P250~(E)P500
3.0kg
161~330
3.0kg
(E)P550~(E)P900
5.0kg
2
2.0 kg
331~390
3.5kg
391~480
4.5kg
481~630
5.0kg
631~710
6.0kg
711~800
8.0kg
801~890
9.0kg
891~1070
10.0kg
1071~1250
12.0kg
1251~
14.0kg
<Example>
Indoor
1: 80
A: ø28.58
40 m
a: ø9.52
10 m
At the
conditions
below:
2: 250 B: ø9.52
10 m
b: ø9.52
5 m
3: 32
C: ø9.52
20 m
c: ø6.35
5 m
4: 40
D: ø9.52
5 m
d: ø6.35
10 m
5: 32
E: ø9.52
5 m
e: ø6.35
5 m
6: 63
F: ø22.2
3 m
f: ø9.52
5 m
G: ø19.05
1 m
Outdoor
P550
The total length of each liquid line is as follows:
ø28.58: A = 40 m
ø22.2: F = 3 m
ø19.05: G = 1 m
ø9.52: C + D + E + a + b + f = 50 m
ø6.35: c + d + e = 20 m
Therefore,
<Calculation example>
Additional refrigerant charge
=
40
×
0.36 + 3
×
0.23 + 1
×
0.16 + 50
×
0.06 + 20
×
0.024 + 5 + 2 + 5
= 30.8 kg
Limitation of the amount of refrigerant to be charged
The above calculation result of the amount of refrigerant to be charged must become below the value in the table below.
Outdoor unit model
P200
P250
P300
P350
P400
P450
P500
P550
P600
P650
P700
P750
P800
P850
P900
Maximum amount of
refrigerant *1 kg
24.8kg
33.8kg
34.8kg
39.7kg
46.7kg
53.7kg
60.2kg
69.2kg
72.9kg
74.6kg
90.3kg
91.5kg
91.5kg
91.5kg
91.5kg
Outdoor unit model
EP200
EP250
EP300
EP350
EP400
EP450
EP500
EP550
EP600
EP650
EP700
Maximum amount of
refrigerant *1 kg
27.3kg
34.0kg
35.0kg
39.7kg
47.5kg
49.2kg
62.9kg
69.6kg
73.3kg
74.8kg
74.8kg
*1 Amount of additional refrigerant to be charged on site
•