-153-
Checking code
Meaning, detecting method
Cause
Checking method & Countermeasure
Low
pressure
saturation
tempera-
ture
sensor
abnormal-
ity
(Variable
Capacity
unit)
(TH2)
Liquid
level
detecting
tempera-
ture
sensor
abnormal-
ity (TH4)
Liquid
level
detecting
tempera-
ture
sensor
abnormal-
ity (TH3)
1111
1112
1113
1. When saturation temperature
sensor (TH2) or liquid level de-
tecting temperature sensors
(TH3, TH4) detects -40˚C or
less (the first time) during op-
erations, outdoor unit stops
once, mode is changed to re-
start mode after 3 minutes, then
the outdoor unit restarts.
2. When -40˚C or less temp. is
detected again (the second
time) within 30 minutes after
stop of outdoor unit, error stop
is observed with code Nos.
“1111,” “1112,” or “1113” dis-
played.
3. When -40˚C or less tempera-
ture is detected 30 or more min-
utes after stop of outdoor unit,
the stop is regarded as the first
time and the process shown in
1. is observed.
4. 30 minutes after stop of outdoor
unit is intermittent fault check
period with LED displayed.
Note:
1. Low press. saturation tem-
perature trouble is not de-
tected for 3 minutes after
compressor start, and finish
of defrosting operations, and
during defrosting operations.
2. In the case of short/open of
TH2~TH4 sensors before
starting of compressor or
within 10 minutes after start-
ing of compressor, “1111,”
“1112,” or “1113” is displayed
too.
See Refrigerant amount check.
Check operating conditions and
operation status of outdoor unit.
Perform actual operation of cooling
and heating and check operation
satus. (Check operation of LEV)
Cooling-indoor unit LEV, LEV1
Heating-indoor unit LEV
SV5b (whether or not is closed)
21S4b (whether or not it is closed)
1) Gas leak, Gas shortage.
2) Insufficient load operations.
3) Poor operations of indoor LEV.
4) Poor operations of Outdoor
LEV1:
5) Solenoid valve trouble
5V5b:
Lo
w pressure satur
ation temper
ature troub
le
Confirm that ball valve is fully opened.
Check indoor unit, and take measu-res
to troube.
Check outdoor unit, and take measures
to trouble.
Check outdoor unit fan.
See Trouble check of outdoor unit
fan.
See Trouble check of solenoid valve.
Check resistance of thermistor.
See Trouble check of pressure sen-
sor.
Check inlet temp. and press. of sensor
by LED monitor.
6) Poor operations of ball valve.
7) Short cycle of indoor unit.
8) Clogging of indoor unit filter.
9) Fall in air volume caused by dust
on indoor unit fan.
10)Dust on indoor unit heat exchanger.
11)Indoor unit block, Motor trouble.
9)~11) : Fall in low pressure
caused by evaporating capac-
ity in cooling-only cooling-prin-
cipal operation.
12)Short cycle of outdoor unit.
13)Dust on outdoor heat exchanger.
14)Indoor unit fan block, motor trouble,
and poor operations of fan control-
ler.
12)~14): Fall in low press.
caus-ed by lowered evaporat-
ing capa-city in heating-only
heating-principal operation.
15)Poor operations of solenoid valve
SV22/32.
Full load operation during unload.
All but model PUHY-(P)400.
Cannot control low pressor drop
with bypass valve(SV4).
18)Thermistor trouble (TH2~TH6).
19)Pressure sensor abnor
16)Poor operation of solenoid valve
contactor 52C2.
17)Poor operation of solenoid valve
SV4.
mality.
20)Control circuit board thermistor
abnormality and pressure sensor
input circuit abnormality.
21)Poor mounting of ther mistor
(TH2~TH6).
See Trouble check of LEV and
solenoid valve.
cooding
Heating
21S4b:
Heating
Содержание 500YEMK-A
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 207: ... 204 ...