-112-
Detects the outdoor air temperature.
Performs fan control, liquid level
heater control, opening settings of
LEV for oil return and other functions.
Thermistor
R
0
= 15 k
Ω
B
1/80
= 3460
Rt =
15exp{3460( - )}
0
°
C: 15 k
Ω
10
°
C: 9.7 k
Ω
20
°
C: 6.4 k
Ω
25
°
C: 5.3 k
Ω
30
°
C: 4.3 k
Ω
40
°
C: 3.1 k
Ω
Resistance check
TH6
(Outdoor
temperature)
TH7
TH8
TH9a
(SC control)
(P400,
P500 only)
Name
Code
(Function)
Inspection method
Application
Product code
Specification
1
273+t
1
273
1
273+t
1
273
1
273+t
1
273+120
1
273+t
1
323
Resistance check
TH3
TH4
(Liquid level
detection)
TH5
(Liquid pipe
temperature)
Detects liquid level of refrigerant inside
accumulator using the differences
among TH2, TH3, TH4.
1
Frequency control.
2
Controls defrosting during heating.
Resistance check
Conductivity test
using tester
TH10c
(P400,
P500 only)
1) Detects the compressor shell
temperature.
2) Provides compressor shell over-
heating protection.
Inverter cooling fan control using THHS
temperature.
1
Capacity control of high/low
pressure bypass when starting and
stopping.
2
Discharge pressure rise suppression.
Switching of capacity control valve inside
No. 2 compressor (Switching between
full load operation and unload operation)
(All but 400).
Capacity control and controlling the rise
of high-pressure (Back-up of frequency
control).
R
120
= 7.465 k
Ω
B
25/120
= 4057
Rt =
7.465exp
{4057( - )}
20
°
C: 250 k
Ω
70
°
C:
34 k
Ω
30
°
C: 160 k
Ω
80
°
C:
24 k
Ω
40
°
C: 104 k
Ω
90
°
C: 17.5 k
Ω
50
°
C: 70 k
Ω
100
°
C: 13.0 k
Ω
60
°
C: 48 k
Ω
110
°
C: 9.8 k
Ω
R
50
= 17 k
Ω
B
25/120
= 4170
Rt =
17exp {4170 ( - )}
0
°
C: 181 k
Ω
10
°
C: 105 k
Ω
20
°
C: 64 k
Ω
25
°
C: 50 k
Ω
30
°
C: 40 k
Ω
40
°
C: 26 k
Ω
AC 220 to 240 V
Open : conducting
Close: not conducting
AC 220 to 240 V
Close: conducting
Open : not conducting
AC 220 to 240 V
Open : conducting
Close: not conducting
THHS inverter
heat sink tem-
perature
SV1
discharge-
suction
bypass
SV22
capacity
control (full
load)
SV32
capacity
control
(unload)
SV4
discharge-
suction
bypass
TH9b
Controls LEV using temperature
differences among TH5, TH7, TH8
and TH9a.
1) Detects the CS circuit fluid tempera-
ture.
2) Calculates the refrigerant circulation
configuration.
R
0
= 15 k
Ω
B
1/80
= 3460
Rt =
15exp{3460( - )}
0
°
C: 15 k
Ω
10
°
C: 9.7 k
Ω
20
°
C: 6.4 k
Ω
25
°
C: 5.3 k
Ω
30
°
C: 4.3 k
Ω
40
°
C: 3.1 k
Ω
Solenoid
valve
Outdoor unit (Variable capacity unit)
1
2
Performs constant capacity unit LEV2
control by comparing the temperature
difference with low pressure saturation
temperature.
TH10a
TH10b
Heat
exchanger
Gas tempera-
ture
Содержание 500YEMK-A
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 207: ... 204 ...