-168-
Checking
code
6607
Meaning, detecting method
No ACK error
When no ACK signal is detected in 6 continuous times with 30 second interval by
transmission side controller, the transmission side detects error.
Note:
The address/attribute shown on remote controller indicates the controller
not providing the answer (ACK).
1
Outdoor
unit (OC)
Indoor
unit (IC)
Remote
controller
(RC)
(1) Single refr
iger
ant system
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
System
compo-
sition
Generating
unit address
Display of
trouble
Detecting
method
Cause
Checking method & countermeasure
No reply
(ACK) at
OC
transmis-
sion to BC
No reply
(ACK) at IC
transmis-
sion to RC
No reply
(ACK) at
RC
transmis-
sion to IC
1) Poor contact of transmission line of OC and IC.
2) Damping of transmission line voltage/signal
by acceptable range of transmission wiring
exceeded.
Farthest:
Less than 200m
Remote controller wiring: Less than 10m
3) Erroneous sizing of transmission line (Not
within the range below).
Wire diameter: 1.25mm
2
or more
4) Faulty control circuit board of OC.
1) When IC unit address is changed or modified
during operation.
2) Faulty or disconnection of transmission wir-
ing of IC.
3) Slipping off of IC unit connector (CN2M).
4) Faulty IC unit controller.
5) Faulty remote controller.
1) Faulty transmission wiring at IC unit side.
2) Faulty transmission wiring of RC.
3) When remote controller address is changed
or modified during operation.
4) Faulty remote controller.
Shut down OC unit power source, and
make it again.
It will return to normal state at an ac-
cidental case.
When normal state can not be re-cov-
ered, check for the 1) ~ 4) of the cause.
Shut down both OC and IC power so-
urces simultaneously for 5 minutes or
more, and make them again.
It will return to normal state at an acci-
dental case.
When normal state can not be re-cov-
ered, check for the 1) ~ 4) of the cause.
Shut down OC power sources for 5 min-
utes or more, and make it again.
It will return to normal state at an acci-
dental case.
When normal state can not be re-cov-
ered, check for the 1) ~ 4) of the cause.
2
3
Содержание 500YEMK-A
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 207: ... 204 ...