-158-
1) Power cord problem
(constant capacity unit is discon-
nected from the power source)
2) Power board fuse (F01, F02) is
blown.
3) Power board is defective
4) Control board is defective
1) Heavy-load operations exceeding the
unit’s capacity.
2) Power source abnormality
a. Power source voltage drop
b. Power source voltage defect
3) Defective power cord
4) Defective compressor
a. Compressor open phase, earth
fault
b. Compressor lock-up
1) There is an open phase in the power
supply (L1, L2, L3, N).
2) The power supply voltage is dis-
torted.
3) A fuse is defective.
4) T01 is defective.
5) The circuit board is defective.
Checking code
Meaning, detecting method
Cause
Checking method & Countermeasure
4106
4108
4115
Power off
abnormality
(Variable
capacity unit)
Over-current
Protection
(Outdoor unit)
Power supply
sync signal
abnormality
1 Cannot operate because the
constant capacity unit is dis-
connected from the power
source.
1 First detection
If the 51C2 is operated during
operation of the No. 2 or No. 3
compressor the outdoor unit
will temporarily stop. After 3
minutes, it will restart.
2 Second detection
After 1 minute since the
above restart, if the 51C2
operates again there will be
an error stop, and “4108” will
be displayed.
3 After the outdoor unit stops
and the No. 2 compressor re-
starts there will be 1 minute
during which the unit is in pre-
liminary error stop mode. The
preliminary error stop display
will blink on the LED.
The frequency cannot be deter-
mined when the power is switched
on.
(The power supply’s frequency
cannot be detected. The outdoor
fan cannot be controlled by phase
control.)
Measure the voltage in each part of
the constant capacity unit
1
2
Power board (CN20)
3
Control board
•
Confirm unit operation conditions
•
Voltage check on power source
terminal block TB1
•
Open phase check
•
•
Power cord check, compressor
resistance check. (Mega-check)
•
Operate in no-load status.
•
Remove the compressor power
cord, check the power cord
insulation and operate.
If there is no abnormality
when 52C2 is turned ON, the
compressor is defective.
the power supply voltage waveform
is distorted from a sine wave, improve
the power supply environment.
If none of the items in 1) to 4) is
applicable, and if the trouble
reappears even after the power is
switched on again, replace the MAIN
board (when replacing the circuit
board, be sure to connect all the
connectors, ground wires, etc.
securely).
4116 Fan speed
abnormality
(motor
abnoramlity)
(Detects only for PKFY-VAM)
1. Detecting fan speed below
180rpm or over 2000rpm dur-
ing fan operation at indoor unit
(first detection) enters into the
3-minute restart prevention
mode to stop fan for 30 sec-
onds.
2. When detecting fan speed be-
low 180rpm or over 2000rpm
again at fan returning after 30
seconsd from fan stopping, er-
ror stop (fan also stops) will be
commenced displaying 4116.
1) Slipping off of fan speed detect-
ing connector (CN33) of indoor
controller board.
2) Slipping off of fan output connec-
tor (FAN1) of indoor power board.
3) Disconnection of fan speed
detecting connector (CN33) of
indoor controller board, or that of
fan output connector (FAN1) of
indoor power board.
4) Filter cologging.
5) Trouble of indoor fan motor.
6) Faulty fan speed detecting circuit
of indoor controller board, or
faulty fan output circuit of indoor
power board.
•
Confirm slipping off of connector
(CN33) on indoor controller
board.
•
Confirm slipping off of connector
(FAN1) on indoor power board.
•
Check wiring for disconnection.
•
Check filter.
•
Check indoor fan motor.
•
When aboves have no trouble.
1) For trouble after operating fan.
Replace indoor controller board.
If not remedied, replace indoor
power board.
2) For trouble without operating fan.
Replace indoor power board.
Check before the breaker, after the
breaker or at the powersupply
terminal blocks TB1A, and if there
is an open phase, correct the
connections.
52C2 connector, power cord check
Power source terminal block(TB1)
To judge failure of the T01, go to
“Individual Parts Failure Judgment
Methods.”
If F1 on the MAIN board, or F3 is
melted, (Resistance between both
ends of the fuse is ), replace the
fuses.
If
Содержание 500YEMK-A
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 207: ... 204 ...