-173-
1) Total capacity of indoor units in the
same refrigerant system exceeds
the following:
2) Erroneous setting of OC model se-
lector switch (SW3-10).
1) The Indoor unit model name (model
code) connected is not connectable.
Connectable range.....20~250
2) Erroneous setting of the switch
(SW2) for setting of model name of
Indoor unit connected.
1) Number of unit connected to termi-
nal block (TB3) for outdoor/indoor
transmission line exceeds limita-
tions given belows:
(3)
System error
Checking
code
7100
7101
7102
Meaning, detecting method
Cause
Checking method & Countermeasure
Total capacity error
Total capacity of indoor units in
the same refrigerant system ex-
ceeds limitations.
Trouble source:
Outdoor unit
Capacity code error
Error display at erroneous con-
nection of Indoor unit of which
model name can not be con-
nected.
Trouble source:
Outdoor unit
Indoor unit
Connected unit count over
Number of units connected in the
same refrigerant system exceeds
limitations.
Trouble source:
Outdoor unit
a) Check for the model total (capacity cord total) of
indoor units connected.
b) Check whether indoor unit capacity code (SW2)
is wrongly set.
For erroneous switch setting, modify it, turn off
power source of outdoor unit, and indoor unit
simultaneously for 5 minutes or more to modify
the switch for setting the model name (capacity
coad).
Check for the model selector switch (Dip switches
SW3-10 on outdoor unit control circuit) of OC.
a) Check for the model name of the Indoor unit
connected.
b) Check for the switch (SW2 if indoor controller
for setting of Indoor unit model name of gener-
ating address. When it is not agreed to the model
name, modify the capacity code while shutting
off the power source of Indoor unit.
❇
The capacity of Indoor unit can be confirmed by
the self-diagnosios function (SW1 operation) of
Indoor unit.
a) Check whether the connection of units to the
terminal block for indoor/outdoor transmission
wiring (TB3) of outdoor unit is not exceeding the
limitation.
(See 1 ~ 3 left.)
b) Check for 2), 3), 4) and 5).
c) Check for the connection of transmission wiring
to the terminal block for centralized control is
erroneously connected to the indoor/outdoor
transmission wiring terminal block (TB3).
1
ON 500, 250
OFF 400,
200
2 3 4 5
SW3
6 7 8 9 10
.....
...
Model
Total capacity
PUHY-(P)400
520
PUHY-(P)500
650
PUHY-(P)600
780
PUHY-(P)650
845
PUHY-(P)700
910
PUHY-(P)750
975
Model
Total Indoor Units
1
Big Y
1-20
2
Super Y
1-32
Содержание 500YEMK-A
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 207: ... 204 ...