-167-
Checking
code
6606
Meaning, detecting method
Cause
Checking method & Countermeasure
1) Data is not properly transmitted due
to casual errouneous operation of
the generating controller.
2) Faulty generating controller.
Communications with transmis-
sion processor error
Communication trouble between
apparatus processor and trans-
mission processor.
Note:
The address/attribute
shown on remote
controller indicates the
controller which has
detected error.
Turn off power sources of indoor unit, and outdoor
unit.
When power sources are turned off sepa-
rately, microcomputer is not reset and nor-
mal operations can not be restored.
Controller trouble is the source of the trouble
when the same trouble is observed again.