-118-
Example PUHY-P600YSEM-A
ø
12.7
(3 m)
ø
15.88
(1 m)
ø
19.05
(30 m)
ø
15.88
(10 m)
ø
12.7 (20 m)
ø
12.7 (10 m)
ø
12.7
(10 m)
ø
9.52
(10 m)
ø
9.52
(10 m)
ø
6.35
(10 m)
ø
9.52
(20 m)
ø
9.52
(10 m)
ø
9.52
(10 m)
ø
9.52
(10 m)
Each distribution pipe carries liquid.
ø
19.05: 30 m
= 30 m
ø
15.88: 1 m + 10 m
m
ø
12.7 : 3 m + 10 m + 20 m + 10 m
= 43 m
ø
9.52 : 10 m + 10 m + 20 m + 10 m + 10 m + 10 m = 70 m
ø
6.35 : 10 m
=10 m
From the formula above we find that:
Add. Refrigerant volume = (0.29
×
30) + (0.25
×
11) + (0.12
×
43) + (0.06
×
70) + (0.024
×
10) + 3 = 24.05 kg
The result of this calculation is 24.05 kg, however round to the nearest 0.1 kg:
Add. Refrigerant volume = 24.1 kg.
The total refrigerant level (including the outdoor unit refrigerant charge and the additional volume in the extension pipes)
is over 73 kg, please make the total refrigerant amount = 73 kg.
Original refrigerant amount in the outdoor unit + additional refrigerant amount
73 kg
Example for PUHY-P600YSEM-A
PUHY-P400YEM-A
PUHN-P200YEM-A
Additional refrigerant volume
16 kg
+
6.5 kg
+
51 kg
= 73.5 kg
→
Fix to 73 kg
(Set the additional refrigerant volume to 50.5 kg.)
Model
80
Model
125
Model
32
Model
125
Model
80
Model
63
Model
71
Caution: (R407C)
When charging with refrigerant, be sure to charge from the liquid side. If charging from the gas side, it will cause
the refrigerant composition to change inside the unit and the composition of the refrigerant remaining in the
canister will also change.
= 11
Содержание 500YEMK-A
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 207: ... 204 ...