-161-
Checking code
Meaning, detecting method
Cause
Checking method & Countermeasure
4240
4250
Over load
protection
(Variable
capacity unit)
IPM alarm
output /
Bus voltage
abnormality
Variable
capacity unit
If IAC 32 Amps is detected con-
tinuously for 10 minutes during op-
eration of the inverter after 5 or
more seconds have passed since
the inverter started.
If over current, overheat or
undervoltage of drive cirduit is
detected by IPM during inverter
operation.
[Inverter error detail : 1]
If VDC 300 or VDC 760V
is detected during inverter op-
eration.
[Inverter error detail : 1]
If IAC
39Amps is detected
during inverter operation.
[Inverter error detail : 11]
1) Air passage short cycle.
2) The heat exchanger is clogged.
3) Power supply voltage.
4) External air temperature.
5) Capacity setting error.
6) The solenoid valves (SV1, 2) are
defective, or the solenoid valve
drive circuit is defective.
7) The wiring is defective.
8) Fan motor (MF) operation is defec-
tive.
9) The inverter/compressor is defec-
tive.
1) The power supply voltage is abnor-
mal.
2) The wiring is defective.
3) The inverter / compressor is defec-
tive.
Is the unit’s exhaust short cycling?
Clean the heat exchanger.
If the power supply voltage is less than
342 V, it is outside specifications.
If the external air temperature is over
43 C it is outside the specifications.
• Is the indoor unit capacity total cor-
rect?
• Are the outdoor/indoor unit capac-
ity settings correct?
To judge failure of the solenoid valve,
go to “Individual Parts Failure Judg-
ment Methods” for the “Solenoid Valve.”
Check 1 connections, 2 contact at the
connectors and 3 for broken wires in
the following wiring.
TB1A~NF~TB1B
TB1B~FANCON board~CN04
CNMF~MF
TB1B~CNTR1
CNFC1~CNFC2
Go to “Treating Fan Motor Related
Trouble.”
Go to “Treating Inverter/Compressor
Related Trouble.”
•
Check if an instantaneous stop or
power failure, etc. has occurred.
•
Check if the voltage is the rated
voltage value.”
Check 1, the connections, 2, contact
at the connectors, 3 tightening torque
at screw tightened portions, 4, wiring
polarities, 5, for broken wires, and 6,
for grounding in the following wiring.
TB1A~NF~TB1B, TB1A~DS~[52C,
R1, R5]~[C2, C3]~IPM Wiring
CNDC1 (G / A) ~ CNVDC (INV) Wir-
ing
❇
Check if the wiring polarities are as
shown on the wiring diagram plate.
Go to “Treatment of Inverter/Compres-
sor Related Trouble.
4260 Cooling fan
abnormality
If the heat sink temperature (THHS)
100 C for 20 minutes or longer just
before the inverter starts.
Same as “4230.”
1) Same as “4230.”
Variable
capacity unit
1
2
3
Содержание 500YEMK-A
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 207: ... 204 ...