PL-565
Accumass BW500
Page 99
P
ID Control
Integral Control (Automatic Reset),
I
The
I
term on the BW500 is used to increase or reduce the amount of control output
to eliminate the offset caused by the
P
term. The
I
term acts on the
accumulation
of
the error over small increments of time. As the process reaches setpoint and the
error becomes small, the effect of the
I
term decreases. A higher
I
term makes the
BW500 faster to react to changes, but can also make it less stable.
•
allowable input range:
0.000 to 2.000
•
typical operating range:
0.100 to 0.300
•
default value:
0.200
The
P
and
I
terms together can make a suitable control algorithm and for many
applications, they work fine. However, if faster response to changes is desired, it is
necessary to use larger
P
and
I
terms. Unfortunately, larger terms can make the
system unstable. A derivative term is needed to influence the control output as the
process variable approaches the set point.
Derivative Control (Pre-Act or Rate),
D
The
D
term on the BW500 influences the control output based on changes in the
magnitude and direction of the change in error. If there is a constant error, the
D
term has no effect. As the error gets larger, the
D
term combines with the
P
term to
make the BW500 control output respond faster. When the error is getting smaller,
the
D
term acts to reduce the amount of control output to help prevent overshooting
the set point. In general, a higher
P
term will require a larger
D
term.
+
Error
Setpoint
-
Decreasing
Error
Incr.
Error
Decr.
Error
Increasing
Error
Direction of
Proportional
Action
Direction of
Derivative
Action
•
allowable input range:
0.000 to 1.000
•
typical operating range:
0.010 to 0.100
•
default value:
0.050
The result of the derivative action is that it can make a system more responsive and
more stable at the same time.
Содержание ACCUMASS BW500
Страница 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Страница 6: ...Page 6 Accumass BW500 PL 565...
Страница 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Страница 28: ...Page 28 Accumass BW500 PL 565 Installation...
Страница 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Страница 94: ...Page 94 Accumass BW500 PL 565 Operation...
Страница 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Страница 110: ...Page 110 Accumass BW500 PL 565 Batching...
Страница 112: ...Page 112 Accumass BW500 PL 565 Certification...
Страница 140: ...Page 140 Accumass BW500 PL 565 Appendices...