Accumass BW500
PL-565
Certification
Programming
The pre-warn function is optional.
The setpoint associated with the pre-warn relay is entered in P564, batch setpoint.
The setpoint associated with the batch relay is entered in P567, batch pre-warn
setpoint.
relays:
access P100, relay function
select relay (1 – 5)
select function 7, pre-warn
access P100, relay function
select relay (1 – 5, other than the pre-warn relay)
select function 8, setpoint
batch operation:
access P560, batch mode control
select 1, enable batch operation
access P564, batch setpoint
enter the desired batch total
access P566, batch pre-warn
set to
on
(1) or leave
off
(0)
if batch pre-warn selected,
access P567, batch pre-warn setpoint
enter the pre-warn total
access P568, batch pre-act,
set to off (0), Auto (1), or Manual (2)