Page 76
Accumass BW500
PL-565
Par
am
et
e
rs
Batch Control (P560 – P568)
The following parameters are specific to the use of the BW500 as a batch controller.
Refer to Batch Control.
P560
Batch Mode Control
Enables the batch control function. Batch control is count up.
Entry:
0 = off
f
1 = count up
P564
Batch Setpoint
Sets the batch total. When the amount of material delivered reaches this point, the
batch relay contact opens (P100) to signal the end of the batch.
(
f
=0.000)
Enter the setpoint of the units of weight selected (P005)
P566
Batch Pre-Warn
Enables or disables the pre-warn function associated with batch control, warning that
the batch is nearing completion.
Entry:
0 = off
f
1 = on
P567
Batch Pre-Warn Setpoint
Sets the setpoint for the pre-warn function (P566). When the batch reaches the
setpoint, the relay contact associated with the pre-warn function (P100) closes.
(
f
=0.000)
Enter setpoint in units of weight selected (P005)
P568
Batch Pre-Act
Acts on the batch operation such that when the batch totalizer is reset, the batch total
is compared to the setpoint (P564). The difference is then applied to pre-act on the
setpoint for the next batch in order to improve the accuracy of the batch. The activity
is internally limited to
±
10% of the batch setpoint
Entry:
0 = off
f
1 = Auto
2 = Manual
Содержание ACCUMASS BW500
Страница 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Страница 6: ...Page 6 Accumass BW500 PL 565...
Страница 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Страница 28: ...Page 28 Accumass BW500 PL 565 Installation...
Страница 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Страница 94: ...Page 94 Accumass BW500 PL 565 Operation...
Страница 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Страница 110: ...Page 110 Accumass BW500 PL 565 Batching...
Страница 112: ...Page 112 Accumass BW500 PL 565 Certification...
Страница 140: ...Page 140 Accumass BW500 PL 565 Appendices...