P107
Relay Alarms
Sets the alarm mode for the relay selected, relays 1 to 5 (P100 - 01 to – 05
Entry:
1 = high and low
f
2 = high only
3 = low only
Note:
Not applicable if P100 = 4, 5, 6, 7 or 8.
P117
Relay Dead Band
Sets the dead band for the relay selected, relays 1 to 5 (P100 - 01 to – 05). The dead
band prevents relay chatter due to fluctuations at the high or low setpoint.
(
f
=3.0)
enter the value in % of full scale, or for deviation alarm enter % of setpoint
Note:
Not applicable if P100 = 4, 7 or 8.
P118
Relay Logic
Sets the logic applied to relays to determine their open or closed state.
Power Failure
The relays on the BW500 default to normally open under power loss.
Normal Operation
In software, all relays are programmed the same way; with ‘on’ setpoints always
indicating relay action. This parameter allows the reversal of the operation. Normally,
P118 = 2 for each relay.
Reverse Operation
When P118 = 3, the operation of the indexed relay is reverse from normal.
Values
P118
Logic
Relay
2
positive logic
normally closed
f
3
negative logic
normally open
Содержание ACCUMASS BW500
Страница 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Страница 6: ...Page 6 Accumass BW500 PL 565...
Страница 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Страница 28: ...Page 28 Accumass BW500 PL 565 Installation...
Страница 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Страница 94: ...Page 94 Accumass BW500 PL 565 Operation...
Страница 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Страница 110: ...Page 110 Accumass BW500 PL 565 Batching...
Страница 112: ...Page 112 Accumass BW500 PL 565 Certification...
Страница 140: ...Page 140 Accumass BW500 PL 565 Appendices...