Recal
ib
rat
io
n
Example :
A non-linearity with respect to the ideal response exists in a belt scale application
with design rate of 200 t/h. It is decided to do material tests at 15, 30 , 45, 60 and
75% of the design load. After performing a zero and a span calibration at 100% of the
design load, followed by material tests and manual span adjust, five material tests
were performed at 30, 60, 90, 120 and 150 t/h, as indicated by the BW500. The
following data was tabulated. (This example is exaggerated for emphasis).
The material tests should be run at same belt speed, representative of normal
operation; in this case 1.2 m/s. For each rate, record the corresponding load value by
scrolling to the BW500 load display during running conditions or by calculation.
load = rate
speed
BW500 load
material test
BW500 total
compensation*
kg/m
tonnes
tonnes
%
6.94
2.5
2.8
-10.7
13.89
5.0
4.5
11.1
20.83
7.5
7.9
-5.1
27.78
10.0
9.2
8.7
34.72
12.5
13.3
-6.0
*calculation example: % compensation =
2.5 – 2.8 x 100
2.8
= - 10.7
actual weight per material test
totalized weight by BW500
belt scale response
linearized BW500 response
internal response 100% - 150% of span
% compensation
span (100%)
-6.0
♦
-5.1
♦
-10.7
♦
11.1
♦
8.7
♦
We
ight
= T
onn
es
Load – kg / m
Содержание ACCUMASS BW500
Страница 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Страница 6: ...Page 6 Accumass BW500 PL 565...
Страница 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Страница 28: ...Page 28 Accumass BW500 PL 565 Installation...
Страница 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Страница 94: ...Page 94 Accumass BW500 PL 565 Operation...
Страница 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Страница 110: ...Page 110 Accumass BW500 PL 565 Batching...
Страница 112: ...Page 112 Accumass BW500 PL 565 Certification...
Страница 140: ...Page 140 Accumass BW500 PL 565 Appendices...