PL-565
Accumass BW500
Page 131
Communic
a
tions
Parameter Values
Bit Mapped
Bits are packed into registers in groups of 16 bits (1 word). In this manual we number
the bits from 1 to 16, with bit 1 being the least significant bit and bit 16 referring to the
most significant bit.
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
MSB
LSB
32 Bit
Large numbers are put into unsigned 32 bit integers with a fixed decimal place of
three. For example, a value of ‘7345’ represents a value in the BW500 ‘7.345’. The
default word order is that the first word is the most significant word (MSW) and the
second word (register) is the least significant word (LSW).
For example, if we read R41,431 as a 32-bit, the 32 bits would look like the following:
R41,431
R41,432
16
MSB
1
16
LSB
1
32
32-bit integer value (UINT32)
1
The whole is read as a 32-bit integer.
The most significant byte (MSB) and least significant byte (LSB) can be reversed to
accommodate some Modbus drivers. See Format Word for BW-500 on page 125 for
details.
Text Messages
If a Milltronics device parameter returns a text message, that message is converted
to a number and provided in the register. The numbers are shown in the table below:
Number
Text Message as displayed on LCD
22222
invalid value
30000
off
30001
on
30002
≡
≡
≡
≡
30003
(parameter does not exist)
30004
err
30005
err1
30006
open
30007
shrt
Содержание ACCUMASS BW500
Страница 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Страница 6: ...Page 6 Accumass BW500 PL 565...
Страница 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Страница 28: ...Page 28 Accumass BW500 PL 565 Installation...
Страница 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Страница 94: ...Page 94 Accumass BW500 PL 565 Operation...
Страница 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Страница 110: ...Page 110 Accumass BW500 PL 565 Batching...
Страница 112: ...Page 112 Accumass BW500 PL 565 Certification...
Страница 140: ...Page 140 Accumass BW500 PL 565 Appendices...