M‐Thermal Split
201909 79
Procedure
Pd
Air side heat exchanger refrigerant outlet
temperature sensor is loose
1
Yes
Ensure the temperature sensor is
connected properly
No
Air side heat exchanger refrigerant outlet
temperature sensor has short‐circuited
or failed
2
Yes
Replace the temperature sensor
No
The air side heat exchanger heat
exchange is poor
3
Yes
Inspect the system and fix the error
No
The fan or fan motor is blocked or
damaged
Yes
Inspect the system and fix the error
No
Replace outdoor main PCB
Notes:
1.
Air side heat exchanger refrigerant outlet temperature sensor and outdoor ambient temperature sensor connection port are CN9 on the outdoor unit main
PCB ( labeled 12 in Figure 4‐2.2 in Part4, 2.3 "Main PCBs for Refrigerant System, Inverter Module")..
2.
Measure sensor resistance. If the resistance is too low, the sensor has short‐circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1.1 “Outdoor Unit Layout” and to Table 4‐5.1 in Part 4, 5.1 “Temperature Sensor Resistance
Characteristics”.
3.
Check air side heat exchanger, fan and air outlets for dirt/blockages.
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...