Piping Diagrams
2.1
Outdoor Unit Piping
MHA‐V4W/D2N8 / MHA‐V6W/D2N8 / MHA‐V8W/D2N8 / MHA‐V10W/D2N8
Figure 2‐2.1: MHA‐V4(6,8,10)W/D2N8 piping diagram
Legend
1
Compressor
7
Electronic expansion valve
2.1
Discharge pipe temperature sensor
8
Stop valve (liquid side)
2.2
Outdoor ambient temperature sensor
9
Stop valve (gas side)
2.3
Air side heat exchanger refrigerant outlet temperature sensor
10
Pressure sensor
2.4
Suction pipe temperature sensor
11
Separator
3
4‐way valve
12.1
Low pressure switch
4
Air side heat exchanger
12.2
High pressure switch
5
Distributor
13
Capillary
6
Filter
14
Solenoid valve
Key components:
1.
Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
2.
Four‐way valve:
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the air side heat
exchanger functions as a condenser and water side heat exchanger functions as an evaporator; when open, the air
side heat exchanger functions as an evaporator and water side heat exchanger function as a condenser.
3.
High and low pressure switches:
Regulate refrigerant system pressure. When refrigerant system pressure rises above the upper limit or falls below the
lower limit, the high or low pressure switches turn off, stopping the compressor.
4.
Separator:
Separates liquid refrigerant from gas refrigerant to protect compressor from liquid hammering.
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...