M‐Thermal Split
18 201909
Midea M‐Thermal Split Ser
vice Manual
3.3
Startup Control for Heating and Domestic Hot Water Operation
Table 3‐3.1: Component control during startup in heating and domestic hot water modes
Component
Wiring diagram
label
4‐10kW
Control functions and states
Inverter compressor
COMP
●
Compressor startup program selected according to
ambient temperature
1
DC fan motor
FAN
●
Fan run at maximum speed
2
Electronic expansion valve
EXV
●
Position (steps) from 0 (fully closed) to 480 (fully open),
controlled according to outdoor ambient temperature,
discharge temperature, suction superheat, compressor
speed and refrigerant system pressure
Four‐way valve
4‐WAY
●
On
Notes:
1.
Refer to Figure 3‐3.1, Figure 3‐3.2 in Part 3, 3.2 “Compressor Startup Program”.
2.
Refer to Table 3‐4.1 in Part 3, 4.6 “Outdoor Fan Control”.
3.4
Startup Control for Cooling Operation
Table 3‐3.2: Component control during startup in cooling mode
Component
Wiring diagram
label
4‐10kW
Control functions and states
Inverter compressor
COMP
●
Compressor startup program selected according to
ambient temperature
1
DC fan motor
FAN
●
Fan run at maximum speed
2
Electronic expansion valve
EXV
●
Position (steps) from 0 (fully closed) to 480 (fully open),
controlled according to outdoor ambient temperature,
discharge temperature, suction superheat, compressor
speed and refrigerant system pressure
Four‐way valve
4‐WAY
●
Off
4
Normal Operation Control
4.1
Component Control during Normal Operation
Table 3‐4.1: Component control during heating and domestic hot water operations
Component
Wiring diagram
label
4‐10kW
Control functions and states
Inverter compressor
COMP
●
Controlled according to load requirement from hydronic
system
DC fan motor
FAN
●
Controlled according to outdoor heat exchanger pipe
temperature
Electronic expansion valve
EXV
●
Position (steps) from 0 (fully closed) to 480 (fully open),
controlled according to outdoor ambient temperature,
discharge temperature, suction superheat, compressor
speed and refrigerant system pressure
Four‐way valve
4‐WAY
●
On
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...