Table 4‐3.1: Error code table
(continued)
H8
47
Pressure sensor error
User interface and outdoor
unit main PCB
H9
48
Circuit 2 water outlet temperature sensor error
User interface and hydronic
box main PCB
Sensor T1B
HA
49
Water side heat exchanger water outlet
temperature sensor error
User interface and hydronic
box main PCB
Sensor Tw_out
HF
54
Refrigerant system EEPROM error
User
interface
and
refrigerant system main PCB
P0,
HP
20
57
Low pressure protection
User
interface
and
refrigerant system main PCB
P1
21
High pressure protection
User
interface
and
refrigerant system main PCB
P3
23
Compressor current protection
User interface and outdoor
unit main PCB
P4
24
Discharge temperature protection
User interface and outdoor
unit main PCB
P5
25
High temperature difference between water side
heat exchanger water inlet and water outlet
temperatures protection
User interface and hydronic
box main PCB
P6
H4
26
43
Inverter module protection
User interface
Displayed on user interface
when any of L0, L1, L2, L4,
L5, L7, L8 or L9 occur
L0
‐
Inverter module protection
Outdoor unit main PCB
L1
‐
DC bus low voltage protection
Outdoor unit main PCB
L2
‐
DC bus high voltage protection
Outdoor unit main PCB
L4
‐
MCE error
Outdoor unit main PCB
L5
‐
Zero speed protection
Outdoor unit main PCB
L7
‐
Phase sequence error
Outdoor unit main PCB
L8
‐
Compressor frequency variation greater than
15Hz within one second protection
Outdoor unit main PCB
L9
‐
Actual compressor frequency differs from target
frequency by more than 15Hz protection
Outdoor unit main PCB
Pb
31
Water side heat exchanger anti‐freeze
Hydronic box main PCB
Pd
33
High temperature protection of refrigerant outlet
temperature of condenser in cooling mode
User interface and outdoor
unit main PCB
PP
Hb
38
50
Water side heat exchanger inlet temperature is
higher than outlet temperature in heating mode
User interface and hydronic
box main PCB
Notes:
1.
When the error code appears, the error code corresponding to the serial number can be obtained through the H1H2 port by using the host
computer to query the wired controller register.
2.
Sensor names in this service manual referring to refrigerant flow is named according refrigerant flow during cooling operation refer to Part 2, 3
“Refrigerant Flow Diagrams”.
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...