M‐Thermal Split
52
201909
Midea M‐Thermal Split Ser
vice Manual
4.8
HF Troubleshooting
Digital display output
Description
Outdoor unit main PCB EEPROM error.
M‐Thermal Split stops running.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes
Outdoor unit main PCB EEPROM is not connected properly.
Outdoor unit main PCB damaged.
Procedure
HF
Outdoor unit EEPROM
1
is not connected
properly
Yes
Ensure the EEPROM is connected
properly
No
Replace outdoor unit main PCB
Notes:
1.
Outdoor unit EEPROM is designated IC23 on the outdoor unit main PCB (labeled 29 in Figure 4‐2.2 in Part4, 2.3 "Main PCBs for Refrigerant System, Inverter
Module").