M‐Thermal Split
36
201909
Midea M‐Thermal Split Ser
vice Manual
2.4
Check Buttons
Refrigerant system SW2 check button
Button SW2 is used to check the parameters of the refrigerant system. Refer to Table 4‐2.2 First, press Button SW2 for 3
seconds and the first parameter (operating mode) will be displayed. Then, on each subsequent press, the next parameter
is displayed.
Table 4‐2.4: SW2 system check
Number Parameters displayed on digital display
Remarks
1
Mode
0: standby; 2: cooling; 3: heating; 4 forced cooling.
2
Fan speed
The fan speed index is related to the fan speed in rpm as described in Table 3‐4.1 in Part 3, 4.6
“Outdoor Fan Control”.
3
Capacity requirements
Compressor frequency
4
Capacity requirements(Correct)
Compressor frequency
5
Frequency limit code
0: Without restriction
1: Compressor frequency restriction by o
utdoor ambient temperature
2:
Compressor frequency restriction by c
ondenser temperature
3:
Compressor frequency restriction by actual c
urrent
4:
Compressor frequency restriction by
voltage AC
5:
Compressor frequency restriction by
radiator temperature
6:
Compressor frequency restriction by
Discharge temperature
7:
Compressor frequency restriction by pressure
6
T3: Condenser temperature (°C)
When no decimal point is displayed:
Temperature is ≥ ‐9°C
Actual value = value displayed
When decimal point is displayed between the two digits:
Temperature is ≤ ‐10°C
Actual value = value displayed x ‐10
Example: “1.2” indicates ‐12°C
7
T4: Outdoor ambient temperature (°C)
8
Tp: Discharge temperature (°C)
When the temperature < 100 °C, actual value = value displayed. When the
temperature
≥
100 °C, actual value = value displayed × 10
9
Th: Suction temperature (°C)
When no decimal point is displayed:
Temperature is ≥ ‐9°C
Actual value = value displayed
When decimal point is displayed between the two digits:
Temperature is ≤ ‐10°C
Actual value = value displayed x ‐10
Example: “1.2” indicates ‐12°C
10
TF: Radiator temperature (°C)
Actual value = value displayed
11
Electric Expansive Valve
Steps = value displayed × 8
12
Actual current
Actual value = value displayed
13
Compressor current
Actual value = value displayed
14
Voltage AC
Actual value = value displayed × 10
15
Voltage DC
Actual value = value displayed × 10
16
Pressure
Actual value = value displayed
17
Software version
Version number
18
Last fault
“nn” is displayed if no error or protection events have occurred since start‐up
19
‐‐
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...