Special Control
6.1
Oil Return Operation
In order to prevent the compressor from running out of oil, the oil return operation is conducted to recover oil that has
flowed out of the compressor and into the refrigerant piping. When the oil return operation is being conducted, the
outdoor unit refrigerant system main PCB displays code d0.
The oil return operation starts when the following condition occurs:
When the compressor cumulative operating time with running rotation speed less than 42rps reaches 6 hours.
The oil return operation ceases when any one of the following three conditions occurs:
Oil return operation duration reaches 5 minutes.
Compressor stops.
Tables 3‐6.1 show component control during oil return operation in cooling mode.
Component
Wiring diagram
label
4‐10kW
Control functions and states
Inverter compressor
COMP
●
Runs at oil return operation rotation speed
DC fan motor
FAN
●
Controlled according to cooling mode
Electronic expansion valve
EXV
●
304 (steps)
Four‐way valve
4‐WAY
●
Off
Tables 3‐6.2 show component control during oil return operation in heating and DHW modes.
Component
Wiring diagram
label
4‐10kW
Control functions and states
Inverter compressor
COMP
●
Runs at oil return operation rotation speed
DC fan motor
FAN
●
Controlled according to heating mode
Electronic expansion valve
EXV
●
304 (steps)
Four‐way valve
4‐WAY
●
On
6.2
Defrosting Operation
In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit air side heat exchanger
is performing as a condenser. The defrosting operation is controlled according to outdoor ambient temperature, air side
heat exchanger refrigerant outlet temperature and the compressor running time.
Table 3‐6.3: Component control during defrosting operation
Component
Wiring diagram
label
4‐10kW
Control functions and states
Inverter compressor
COMP
●
Runs at defrosting operation rotation speed
DC fan motor
FAN
●
Off
Electronic expansion valve
EXV
●
Fully open
Four‐way valve
4‐WAY
●
Off
6.3
Force Cooling Operation
The force cooling operation helps the refrigerant recovering before removal the water side heat exchanger.
The force cool mode can be ended by pushing the button on the outdoor refrigerant system main PCB named “force‐cool”
for 5s or this mode will be ended automatic if the system has operated force cool mode for more than 30 minutes.
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...