H7 Troubleshooting
Digital display output
Description
Abnormal main circuit voltage.
M‐Thermal Split stops running.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes
Power supply voltage not within 90%~110% of rated voltage.
Outdoor unit main PCB is damaged.
Procedure
H7
Power supply voltage is not within
90%~110% of rated voltage
Yes
Provide normal power supply
No
Replace outdoor unit main PCB