M‐Thermal Split
66
201909
Midea M‐Thermal Split Ser
vice Manual
4.17
P4 Troubleshooting
Digital display output
Description
Discharge temperature protection.
When the compressor the discharge temperature rises above 115°C, the system displays P4 protection and
M‐Thermal Split stops running. When the discharge temperature falls below 90°C, P4 is removed and normal
operation resumes.
Error code is displayed on refrigerant system main PCB and user interface.
Possible causes
Temperature sensor error
High pressure side blockage.
Poor condenser heat exchange.
Outdoor unit main PCB damaged.
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...