Outdoor Fan Control
The speed of the outdoor unit fan is adjusted in steps, as shown in Table 3‐4.1.
Table 3‐4.1: Component control during cooling operation
Fan speed index
Fan speed (rpm)
4kW
6kW
8kW
10kW
W1
300
300
300
300
W2
340
340
340
340
W3
400
400
400
400
W4
450
450
450
450
W5
520
520
520
520
W6
580
580
580
580
W7
630
630
630
630
W8
680
680
680
680
W9
730
730
730
730
5
Protection Control
5.1
High Pressure Protection Control
This control protects the refrigerant system from abnormally high pressure and protects the compressor from transient
spikes in pressure.
Figure 3‐5.1: High pressure protection control
Notes:
1.
P
c
: Discharge pressure
When the discharge pressure rises above 4.2MPa the system displays P1 protection and the unit stops running. When the
discharge pressure drops below 3.2MPa, the compressor enters re‐start control.
5.2
Low Pressure Protection Control
This control protects the refrigerant system from abnormally low pressure and protects the compressor from transient
drops in pressure.
Figure 3‐5.2: Low pressure protection control
Notes:
1.
P
e
: Suction pressure
P
c
> 4.2MPa
P
c
< 3.2MPa
Normal operation
High pressure protection, error code P1 is displayed
P
e
< 0.14MPa
P
e
> 0.30MPa
Normal operation
Low pressure protection, error code P0 is displayed
When P0 protection occurs 3 times
in 60 minutes, the HP error is
displayed. When an HP error occurs,
a manual system restart is required
before the system can resume
operation.
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...