M‐Thermal Split
12 201909
Midea M‐Thermal Split Ser
vice Manual
2.2
Hydronic box Piping
SMK‐60/CGN8 / SMK‐80/CGN8
Figure 2‐2.2: SMK‐60/CGN8 / SMK‐80/CGN8 piping diagram
Legend
1
Water side heat exchanger
9
Water pump
2
Water flow switch
10
Manometer
3
Refrigerant liquid line temperature sensor
11
Safety valve
4
Refrigerant gas line temperature sensor
12
Refrigerant gas side
5
Water outlet temperature sensor
13
Refrigerant liquid side
6
Water inlet temperature sensor
14
Water outlet
7
Air purge valve
15
Water inlet
8
Expansion vessel
Key components:
1.
Air purge valve:
Automatically removes air from the water circuit.
2.
Safety valve:
Prevents excessive water pressure by opening at 43.5 psi (3 bar) and discharging water from the water circuit.
3.
Expansion vessel:
Balances water system pressure. (Expansion vessel volume: 3L.)
4.
Water flow switch:
Detects water flow rate to protect compressor and water pump in the event of insufficient water flow.
5.
Backup electric heater:
Provides additional heating capacity when the heating capacity of the heat pump is insufficient due to very low
outdoor temperature. Also protects the external water piping from freezing.
6.
Manometer:
Provides water circuit pressure readout.
7.
Water pump:
Circulates water in the water circuit.
2
11
3
4
5
6
7
1
8
9
10
12
11
13
14
15
F
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...