M‐Thermal Split
42
201909
Midea M‐Thermal Split Ser
vice Manual
4.2
E0, E8 Troubleshooting
Digital display output
Description
Water flow failure.
E0 indicates E8 has displayed 3 times. When an E0 error occurs, a manual system restart is required before the system
can resume operation.
M‐Thermal Split stops running.
Error code is displayed on hydronic box main PCB and user interface.
Possible causes
The wire circuit is short connected or open.
Water flow rate is too low.
Water flow switch damaged.
Midea CAC Confidential