M‐Thermal Split
201909 55
4.10
H1 Troubleshooting
Digital display output
Description
Communication error between outdoor unit main control board and inverter module.
M‐Thermal Split stops running.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes
Power supply abnormal.
Interference from a source of electromagnetic radiation.
Outdoor unit main PCB or inverter driven module damaged.
Procedure
H1
LED on the main control board of
outdoor unit and inverter module are
light
Yes
LED is not light, the board is
damaged,or have short circuit
No
Communicatin wires between the main
control board of outdoor unit and
inverter module is loose
Yes
Reconnect the communicatin wires
No
There is a source of electromagnetic
radiation near the unit, such as
high‐frequency transmitter or other high
strength radiation device
Yes
Remove the source of interference
No
Replace outdoor unit main PCB and
inverter driven module in turn
Midea CAC Confidential
Содержание SMK-60/CGN8
Страница 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Страница 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...