P3 Troubleshooting
Digital display output
Description
Compressor current protection.
When the compressor current rises above the protection value (4/6kW models 18A, 8/10kW model 19A), the system
displays P3 protection and M‐Thermal Split stops running. When the current returns to the normal range, P3 is
removed and normal operation resumes.
Error code is displayed on refrigerant system main PCB and user interface.
Possible causes
Poor condenser heat exchange.
High pressure side blockage.
Inverter module damaged.
Compressor damaged.
Outdoor unit main PCB damaged.