VERTICAL THROUGH-THE ROOF VENTING
The maximum vertical run of vent pipe is 50 ft. from the top of the fireplace. Maintain 1" air space clearances on all sides of
vents (3" above horizontal runs).
If an offset is required directly on top of the fireplace, two 45
o
elbows may be connected directly to the top of this fireplace to
create a horizontal offset then to run upwards vertically. Doing so will continue to allow the use of the 50 feet maximum vertical
run. If an offset is necessary, it is important to support the vent pipe every 3 ft. to avoid excessive stress on the elbows and
possible separation. Wall straps are available for this purpose.
The FV46 Fireplace must be installed by a qualified Mendota approved serviceperson.
1.
Place the fireplace in its desired location. Drop a plum bob from the ceiling to the position of the fireplace flue exit. Mark the
location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plum bob from the roof to the hole
previously drilled in the ceiling. Mark and drill the spot where the vent will penetrate the roof. Determine if ceiling joists, roof
rafters or other framing will obstruct the venting system. You may wish to relocate the fireplace or to offset, to avoid cutting load
bearing members.
2.
Cut and frame a 10 ½” x 10 ½” opening (for use with a mandatory ceiling fire stop) in the ceiling centered on the hole drilled in
Step No. 1.
3.
To determine the length of the vent pipe required, measure the distance from the fireplace flue outlet to the ceiling, the ceiling
thickness and the vertical rise in the attic or second story and allow sufficient vent height above roofline. For two story
installations, fire stops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be
required.
4.
Assemble the desired lengths of vent pipe and elbows to reach from the fireplace flue outlet. Ensure that all vent pipe and
elbow connections are in their fully twist-lock position and that inner pipe joints are sealed and are leak-proof. Maintain 1"
airspace clearances to combustibles (3" above horizontal runs). Cut a 10" x 10" opening in the roof, centered in the small
drilled hole placed in the roof in No. 1. The opening should be a sufficient size to meet all clearance requirements. Continue
to assemble lengths of pipe and elbows necessary to reach up through the roofline.
5.
Slip the flashing over the pipe sections protruding through the roof. Secure the base of the flashing to the roof with roofing
nails and seal flashing to roof. Ensure the roofing material overlaps the top edge of the flashing. Verify you have at least the
minimum clearance to combustibles at the roofline.
6.
Continue to add pipe sections until the pipe and the vent cap meet the minimum building code requirements, as outlined in
No. 8 on the following page.
For multi-story vertical installation, a ceiling fire stop is required at the second floor and any subsequent floors. The opening
should be framed to 10" x 10" inside dimensions as described in step No. 4.
Add an attic insulation shield to keep attic insulation materials away from vent pipe.
Vertical Pipe runs must be supported using wall straps every 3 feet.
7.
Any occupied areas above the first floor, including closets and storage spaces, which the vertical vent passes through, must be
enclosed. The enclosure may be framed, and sheet rocked with standard construction materials, however, be sure to
maintain minimum allowable clearances between the outside of the vent pipe and the combustible surfaces of the enclosure.
8.
Height "*H" from roof surface to the top of vent cap can be
determined by the table.
9.
Complete installation with storm collar and vent cap.
"H" DIMENSION
ROOF PITCH
FEET
METERS
FLAT to 6/12
2
.6
7/12 to 9/12
2
.6
10/12 to 12/12
4
1.2
13/12 to 16/12
6
1.8
17/12 to 21/12
8
2.4