85-03-01108
FV46
Page
61
4.11
VENTING
WARNING: Proper installation of the vent system, as required in this manual, is vital to the performance of
this Fireplace. Oversights or failure to conform to all installation requirements will void the applicable
warranty.
The FV46 Fireplace must be vented to the outside and must use a rigid coaxial ducting system.
This heater must be properly connected to a venting system in accordance with the manufacturer's
installation instructions. Operation of this heater when not connected to a properly installed and maintained
venting system can result in carbon monoxide (CO) poisoning and possibly death.
If the vent system of this appliance is disconnected for any reason, the vent and air intake systems must be
properly reassembled and resealed before this appliance is put into use.
CAUTION:
Each installation must conform to all local, state and national codes. Refer to the national fuel
gas code and local zoning and code authorities for details on installation requirements. The Mendota
Fireplaces must be vented to the outside in accordance with the latest edition of the National Fuel Gas Code.
In the absence of local codes, the installation must conform with National Fuel Gas Code ANSI Z223.1 (NFPA
54), or Canadian Code CAN1-B149 or most current edition, also known as NFPA 54. Do not connect this
Fireplace to a chimney flue serving a separate solid fuel or gas-burning appliance.
Do Not Use any silicone sealants at pipe joints. Stove gasket cements may be used at pipe joints but is not
required.
Required Clearances to Vent Pipes
•
Clearance to top of a horizontal vent pipe or the top of a horizontal discharge elbow shall be 3” minimum.
•
Clearance to the sides of a horizontal vent pipe and elbows shall be 1” minimum.
•
Clearance to the bottom of a horizontal vent pipe and elbows shall be 1” minimum.
Wall Thimble Information
A wall thimble is required to be installed when penetrating any combustible wall, regardless of whether the wall Is an internal
wall or an external wall.
Wall thimbles are designed to reduce the required clearances to the exterior surfaces of the vent pipe that pass through
combustible walls. The hole size that is specified to be cut in the wall for installation of the wall thimble takes into consideration
the reduced clearance requirement.