Technical Manual
–
Central Operation Unit Smart
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
97
97
Presentation
Single-button function
Two-button function
The display of the function "Send values" depends on the selected data point type. Depending on the
selected data point type, 1-4 different symbols and their color can be selected.
The following table provides an overview of the settings for the various data point types:
Datapoint type
Adjustable symbols
Comment
2 Bit Switch control, DPT 2.001
4 symbols can be set: 1
symbol for each possible state
1 Byte Percent, DPT 5.001
3 symbols can be set for the
ranges 0, 1-229 and 230-255.
Therefore, the button
evaluates the information of
the "Status for display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Decimal fator, DPT 5.005
3 symbols can be set for the
ranges 0%, 1% - 90% and
>90%. Therefore the button
evaluates the information of
the "Status for display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Scene Number, DPT 17.001
1 fixed symbol can be set
2 Byte Colour temperature,
DPT 7.600
1 or 2 symbols can be set: 1
for each switching value
2 Byte Temperature, DPT 9.001
1 fixed symbol can be set
Special presentation possible!
2 Byte Brightness, DPT 9.004
1 fixed symbol can be set
3 Byte RGB value, DPT 232.600
1 fixed symbol can be set
Table 93: Presentation - Send values
Special presentation:
For certain data point types, a special presentation (see table above) is possible. In this presentation,
the status is shown on a larger scale on the display.
The following presentations are possible:
ETS-Text
Dynamic range
[Default value]
Comment
Special display
(DPT 5.001, DPT 5.005)
▪
value as text (0-100%)
▪
value as text (0-255)
▪
link symbol with switching
value
With the settings "value as text"
the text is displayed large on the
display.
Link symbol with switching value
only for 2-button function
Special display
(DPT 9.001)
▪
value as “°C”
▪
value as symbol without unit
▪
value as “K”
▪
link symbol with switching
value
With the settings "value as
symbol" the text is displayed large
on the display.
Link symbol with switching value
only for 2-button function
Table 94: Presentation - Special symbols